House Rewire job

Welcome Guest, Log in or Register
Author 
perplexed

10-22-2005 18:26:38




Report to Moderator

House was built in the 50s.No grounded outlets.Getting ready to sell it.How does a person run 2 wires/ground to the wall outlets etc.?Originally wired through the attic which has very little head room,4/12 pitch roof. Built on crawl space.Want to bring it up to code.Will some drywall have to be cut out to wall switches,high mounted outlets, etc.?Have done a lot of wiring ,but no job like this before.Maybe I should just sell it as is?TIA,perplexed

[Log in to Reply]   [No Email]
T.C. in Tx

10-24-2005 18:44:50




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
I did a shortcut job on an old house a few years ago. In order to use the 3 wire plugs, I changed all of the plugs to the new grounded type, but only hooked up the 2 wires, except the last one before the breaker box.

If you will put a GFI plug in the first plug location (ie--closest to the braker) and run a short wire between the ground and neutral positions on the plug (connect them together) you have the effect of GFI on all plugs on the entire breaker for that set of wiring.

I am sure this doesn"t meet code, but it does make a safer wiring set up than the old two wire plugs ever offered.

That way, any of the plug-ins on the circuit will trip the GFI and cut all of them off. This actually works. Tested it out to be sure since my kids lived in the house for a while.

[Log in to Reply]  [No Email]
buickanddeere

10-26-2005 00:49:38




Report to Moderator
 You did what? Re: House Rewire job in reply to T.C. in Tx, 10-24-2005 18:44:50  
There is no need or reason to tie the ground pin to the neutral on the receptacles downstream of the GFI. The job would meet code as long as the neutral wire always goes to the wide slot and the line to the narrow slot. Old wiring is often poorly marked and it's installation questionable. You could easily tie the line to the receptacle ground pin and energise the case of the electrical device plugged in. Should the GFI fail to work or somebody has swapped the wiring on the GFI "In" vs. the "Out". The GFI will not work and the down stream receptacles have 120V on the ground pins. The code allows three wire receptacles to be used with two wire cabling down stream of the GFI. NO tie to the ground pin at all.

[Log in to Reply]  [No Email]
dr.sportster

10-24-2005 07:23:23




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
There is no rule,law,code or whatever that says you cant sell as is.If the house is wired in bx the cable sheathing is the ground and you can tail off to the box for the three prong receptacle.I would not worry because the next buyer wont appreciate your trouble in doing this.When I sell my house Im sure it will be knocked down.Seems to be builders want to buy and just start new.Older lighting fixtures dont have a ground tail anyhow so forget the lighting at least.

[Log in to Reply]  [No Email]
paul

10-24-2005 06:50:09




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
I would surely let the wiring be unless there was some _real_ reason it needed to be changed.

The only payback you will get on an electrical upgrade is converting a fuse box to a breaker box at the main service - poeple like those, the rest they don't much pay attention to. And, changing out a breaker box is not the best for do-it-yourself, as you can easily get it wrong & create liability issues.

I'd let sleeping dogs lie.

--->Paul

[Log in to Reply]  [No Email]
Hal/WA

10-22-2005 22:51:31




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
Have you opened up some of the outlet boxes and actually looked at the cable to see if it is only 2 wire or if it also has a ground wire in it that may be attached to the metal box? If the wire already has the 3 wires, it isn't much trouble to change the outlet assemblies to the grounded type.

Unless there is some real reason that you could not sell the house with the wiring as-is, I doubt that you could ever recoup your investment to have it rewired. And I would consult a lawyer for an opinion about doing a rewire yourself and then selling the house. You might be increasing your potential liability if something somehow went bad and there was a fire..... I think I would leave it alone. Good luck!

[Log in to Reply]  [No Email]
Stan in Oly, WA

10-22-2005 22:27:06




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
Hi, perplexed

I've done lots of wiring, lots of difficult wiring, and lots of creative wiring, but I always wire to code whether an inspection is involved or not. I can't agree with what john d says about how he ran some of his circuits; if you have to be careful that you don't nail through some of your wiring it isn't right. It has to be where a knowledgeable person will expect it, or protected with metal conduit and nail plates. Working as a remodeling contractor I was never amused to run into any systems where they oughtn't have been. I wouldn't even do it if it was just for myself---and I'm willing to put up with a lot---but you're selling the house. You can't do anything that will create a dangerous situation for someone in the future.

The best advice you've gotten so far was from Davie-OR. His advice is always good, and he knows a lot. You don't have to do anything about the wiring unless you've created some situation that makes it legally necessary.

It took me a long time to get it through my head, but I finally figured out that upgrading your electrical system is one of the poorest payback jobs you can do to sell a house. You'll get twice the money for a twentieth the work with fresh paint. The simple truth is that most people don't know anything about electrical systems, and don't want to. If you really want to do some wiring that matters to most buyers, put phone jacks and cable tv outlets in every room.

I used to love to put in good, sound electrical service upgrades with a few vanity type frills: split kitchen outlets on separate circuits, switched outlets in bedrooms and living rooms, dedicated computer circuits, outlets no more than six feet apart in any room, three-way switches where they were hardly justified. What a colossal waste of time. As far as I can tell, visibly terrible wiring can kill a sale, but great wiring doesn't matter to one person in a thousand.

Post again if there's some reason that you absolutely have to ground your system to sell the house. I suspect that isn't the case because your last line was that maybe you should just sell the house as is. But if you have to, plenty of people on this forum besides me can advise you on how to best go about it.

All the best, Stan

[Log in to Reply]  [No Email]
David - OR

10-22-2005 19:47:40




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
Two wire wiring IS "up to code", provided it was done to the code that existed at the time the wiring was first installed.

You are not required to upgrade the wiring to current new construction practice unless you are doing such an extensive remodel that the studs are exposed and it is thus feasible to pull new wires. (Different localities have different standards on how extensive a remodel triggers such rewiring. But "old wiring" does not, by itself, call for replacement.) It is still legal to continue to use the really old "knob and tube" stuff. Your 1950's era two wire Romex is positively futuristic compared to that.

If the issue is that you can't find a place to plug in three prong cords, or that you feel the bathrooms or kitchens are unsafe without the grounding, there is an exception in the NEC that allows you to retrofit a 3-prong receptacle without providing a ground. The trick is that you must provide a GFI (ground fault interrupter) upstream of any receptacles so converted. There are also certain labeling requirements, since the grounding prong doesn't actually work.

The GFI provides superior safety to a plain, ordinary grounding receptacle without a GFI, and you do not have to pull new wires to the box.

[Log in to Reply]  [No Email]
ed 1

10-23-2005 08:46:58




Report to Moderator
 Re: House Rewire job in reply to David - OR, 10-22-2005 19:47:40  
I'm not sure what your going to accomplish. I don't think the 2 prong outlets are going to lessen the value of your home by much if at all. Vanity - cosmetics will do a lot more and most buyers won't even look for this detail. If you must - GFI's are the way to go at the pannel.

I fixed a few basement outlets so the ground worked properly and had the inspector come in. He said all I had to do was put a GFI braker in the pannel and I'd be in compliance. A lot easer.

[Log in to Reply]  [No Email]
Charles (in GA)

10-22-2005 19:04:43




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
I was faced with this after my father passed away. 1956 surburban house in medium sized town. It had a 60 amp panel and the insurance would not insure under 100 amp, so I replaced the panel, meter socket and disconnect, all cable from weatherhead to the meter to the panel, and pulled new wire from the panel to the first box or junction of each circuit in the house (old wires are never long enough!), left most of the remaining romex in place. I did pull some circuits, most were too difficult to pull to be worth it. I replaced all outlets with new two prong or three prong depending on the wiring, and added a couple of new circuits. Building inspector liked the job, real neat. I sold the house this way (owner finance) and I suppose they are happy with it.

Charles

[Log in to Reply]  [No Email]
john d

10-22-2005 18:38:04




Report to Moderator
 Re: House Rewire job in reply to perplexed, 10-22-2005 18:26:38  
I'm in the process of re-wiring my house, which was built well before 1900. When the REMC electrified the county in 1937, it was wired for 4 circuits. Since then a couple of sub-panels were added and wiring had been done piece-meal.
A few weeks ago, with the help of an electrician, we installed a 200-amp panel, and ran wires for 20+ circuits up through the wall to the upper floor. I pulled the baseboard off the wall and by spacing it out a little over an inch, managed to run all those wires behind it and into the attic. Then I installed a 3'x4' piece of plywood and mounted junction boxes on it. By running the wires from the panel into those boxes, I've set it up so I can then run wires to where I want to in the house.
My house was originally wired with BX armored cable. In a couple of places, two-wire outlets had been replaced with 3-wire by using the metal box and cable armor as the return ground. So far I've had good luck running wires down through walls where needed, and in some cases have pulled them through by tying them onto the old BX cable and using it to drag them to the outlet.
If you have a good working knowledge of wiring fundamentals, you can likely do the job yourself, but you may have to get creative to get the wires to certain places. Sometimes you can run them behind window trim or base boards. Be careful that you don't nail through the wires when re-installing the trim.

[Log in to Reply]  [No Email]
buickanddeere

10-23-2005 06:17:15




Report to Moderator
 Re: House Rewire job in reply to john d, 10-22-2005 18:38:04  
I've seen one of those armoured cable,heating element spiral sheath ground returns. The outer spiral sheath if carrying fault current,just heats up like a heating element until or if the breaker trips



[Log in to Reply]  [No Email]
Eric Rylander

10-23-2005 07:49:03




Report to Moderator
 Re: House Rewire job in reply to buickanddeere, 10-23-2005 06:17:15  
I had to do some re wiring a couple years back- I wanted to put in a heat pump system (reverse cycle AC) and get rid of my leaking propane furnace in the attic. My house had a 100 amp external panel by the meter outside, but I needed a new dedicated 60 circuit to the attic unit's heat strips.

One of the problems was the new panel could not go where the old panel (directly below the meter) was- code needed 3' of unobstructed space in front of the meter, and it had to be between 4'6" and 5'6" to the center of the meter face.

Unfortunately this left me having to put the meter and panel right on the face of my chimmney, sure, I could have gone with an inside panel (meant ripping into walls, more $$) or moved the meter to the other side of the house (meant cutting down a Magnolia tree to re-run the powerlines, and days without power waiting on the electrical co op to come out and move it)

I live in a small enough suburb I could still go down to city hall and pull a "homeowner builder' permit, something you won't be able to do in a lot of areas. I hired two boatyard electricians on the side who charged me $600 labor, and I bought $500 in materials.

To have hired this to a contractor would have cost thousands, and they would not have just run new sub feeds to my still existing fuze box panels inside.

The good thing about this is I now have a 100 amp feed to my detatched garage and running a welder, and a window unit air conditioner in the attatched mother in law apartment does not trip breakers anymore.

But unless you are doing this wiring because some insurance company or FHA is requiring it, it's a waste of your money as far as a return on the investment.

[Log in to Reply]  [No Email]
[Options]  [Printer Friendly]  [Posting Help]  [Return to Forum]   [Log in to Reply]

Hop to:


TRACTOR PARTS TRACTOR MANUALS
We sell tractor parts!  We have the parts you need to repair your tractor - the right parts. Our low prices and years of research make us your best choice when you need parts. Shop Online Today. [ About Us ]

Home  |  Forums


Copyright © 1997-2023 Yesterday's Tractor Co.

All Rights Reserved. Reproduction of any part of this website, including design and content, without written permission is strictly prohibited. Trade Marks and Trade Names contained and used in this Website are those of others, and are used in this Website in a descriptive sense to refer to the products of others. Use of this Web site constitutes acceptance of our User Agreement and Privacy Policy

TRADEMARK DISCLAIMER: Tradenames and Trademarks referred to within Yesterday's Tractor Co. products and within the Yesterday's Tractor Co. websites are the property of their respective trademark holders. None of these trademark holders are affiliated with Yesterday's Tractor Co., our products, or our website nor are we sponsored by them. John Deere and its logos are the registered trademarks of the John Deere Corporation. Agco, Agco Allis, White, Massey Ferguson and their logos are the registered trademarks of AGCO Corporation. Case, Case-IH, Farmall, International Harvester, New Holland and their logos are registered trademarks of CNH Global N.V.

Yesterday's Tractors - Antique Tractor Headquarters

Website Accessibility Policy