welder extension cord

Welcome Guest, Log in or Register
Author 
Keith

01-08-2004 08:27:16




Report to Moderator

I need to make a extension cord (50ft) for my welder. I have that much or more 6/2 G romex on hand. Would it be safe to use this rather than spring a buck or more a foot for 6/3? Reason I ask, I know the G in the 6/2 is significantly thinner. I guess my question is is it NECESSARY to have a 6 guage ground? Will it make any difference?

BTW the existing welder plug is on 6/3 and is 2 feet from the breaker box (50 amp bkr) so the 50 ft is pretty much inclusive of the run for all intent and purpose. TIA

[Log in to Reply]   [No Email]
mike

01-08-2004 22:28:14




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
keith, what ever you do be careful. It may not get you today but it might get you next year.Your life is not worth messing around with.Just make sure you know what your doing.



[Log in to Reply]  [No Email]
Chris Brown

01-08-2004 18:07:05




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
I made me an extension cord for my lincoln ac/dc welder out of romex 10/2 with ground. I can't tell any drop in voltage when I use it even cranked all the way up. The box for the end and the plug cost more than the wire. I know it isn't up to code,but it meets (my code) that is cheap.



[Log in to Reply]  [No Email]
Anonymous Farmers Electri

01-08-2004 17:36:43




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
Although the code is specific in what is ok, there are other things that work such as 3 runs of 12 gauge wire. If I remember correctly 12 gauge wire will support 20 amps so a triple run would thenmake sixty, however I would only recommend this in an extreme pinch and for a very short period of time, and then remove it and have it done right.



[Log in to Reply]  [No Email]
David - OR

01-08-2004 13:50:45




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
Most 220V welders come with three prong plugs. Two are used for power and the third is an equipment grounding conductor. No neutral is used or needed.

A 10AWG equipment grounding conductor is considered adequate for up to a 60 amp circuit. See table 250.122 of the National Electrical Code.

6/2 with ground Romex is adequate electrically, but is woefully inadequate mechanically. There are many code restrictions on how NM cable must be protected and fastened to the building structure, because (amoung other reasons) neither the jacket nor the conductors can tolerate much flexing or rubbing.

If you just want to move the outlet to a different (fixed)location, you can wire the 6/2 w/g over to the new site and install an outlet there. Staple and clamp it properly throughout its length.

If you want a non-fixed extension cord to move around the shop, Romex should be out of the question. The romex will chafe and/or break with any amount of use, creating a fire and shock hazard.

Something like 6/2 W/G SO or SOW hard-service flexible cord would be more appropriate. Install a plug on one end and a socket on the other. You might be able to get by with a lighter than 6 guage wire in the extension cord, depending on the amperage use of your welder.

[Log in to Reply]  [No Email]
JM

01-11-2004 04:59:14




Report to Moderator
 Re: Re: welder extension cord in reply to David - OR, 01-08-2004 13:50:45  
David, Excellent response.
I just made a 50' cable this weekend for the exact same application being discussed. I used 10/4 SA as it was available, and abandoned one conductor.
JM



[Log in to Reply]  [No Email]
Keith

01-09-2004 09:39:13




Report to Moderator
 Re: Re: welder extension cord in reply to David - OR, 01-08-2004 13:50:45  
David,
Thanks for the advice. Rather than make this into a drop cord or move the existing, I hooked to another 50 amp breaker I had on hand and made a new run with the 6/2 and fixed it permanently all along the route. It is slightly more than 50 feet in length and it will help me reach basically any point now in my shop I can weld between the two permanent plugs. the weld leads are quite long to begin with. I did fasten it every 2 feet or so with tie wraps to an existing conduit all the way along the wall. I even saved a male plug now doing it this way and I can put it on another old welder I have. This should have me in business. Thanks to all who replied.

[Log in to Reply]  [No Email]
Matt K

01-08-2004 11:29:55




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
I'm not an electrician, but unless your welder draws more than 50 amps then 6-2 w/ G is what you need. 6-3 or 6-3 with ground is for three CONDUCTORS, not two conductors and a ground. The ground does not need to be the same size as the conductors, since you don't care about voltage drop in the ground, it is simply a safety device.



[Log in to Reply]  [No Email]
Ben in KY

01-08-2004 12:03:41




Report to Moderator
 Re: Re: welder extension cord in reply to Matt K, 01-08-2004 11:29:55  
If the welder has any 110V fans or anything in it that runs off of 110V then the ground is not just a safety device and will be carring current for those 110V devices. This is why the new codes are requiring 3 conductors with ground on 220V appliances and such. With all that said the 6-2/G should work fine for the welder, I use it for an extension cord on mine.



[Log in to Reply]  [No Email]
Matt K

01-08-2004 13:28:18




Report to Moderator
 Re: Re: Re: welder extension cord in reply to Ben in KY, 01-08-2004 12:03:41  
Sorry, but the ground can't be carrying current, that would definitely violate code. Ground and neutral are not the same thing. If you need 110 and 220, then you need 6-3 w/ ground (2 hots, 1 neutral, 1 ground) no exceptions. As far as 220 appliances if they need 110 then they need 6-3 w/ ground for the neutral as well. My welder doesn't need 110 (my fan is 220), it has three wires coming out of it, 2 hots, 1 ground, if your welder has 4 wires coming out of it then you must use 6-3 w/ground. If you are using 6-2 w/ ground and using the ground wire as neutral then your welder is not grounded. It'll work that way, but you could get zapped.

[Log in to Reply]  [No Email]
Ben in KY

01-09-2004 05:53:35




Report to Moderator
 Re: Re: Re: Re: welder extension cord in reply to Matt K, 01-08-2004 13:28:18  
If the welder does not have a place for neutral and ground ( 3 wire plug ) then this is the old way these types of things were wired. If you used 3 wire with ground on this type of equipment, then you would have to hook the neutral and ground on the same terminal if you used 3 wire with ground cable, so I don't see any real safety hazard there. Newer equipment with a 4 wire plug require 3 wires with ground.

[Log in to Reply]  [No Email]
john

01-09-2004 06:33:19




Report to Moderator
 Re: Re: Re: Re: Re: welder extension cord in reply to Ben in KY, 01-09-2004 05:53:35  
No if you have a old style 2 hot 1 netural on a 3 wire plug and you ran a new 4 wire you would NOT hook both the ground and netural to the same spot!!!!! !!!!! !
You would use a 4 wire and hook the netural to the terminal and hook the ground to the case of the welder. Do not use a ground wire as a netural because a ground wire is bare and has no coating. A netural wire is coated so in can carry current back to the fuse box.

[Log in to Reply]  [No Email]
Ben in KY

01-09-2004 11:26:10




Report to Moderator
 Re: Re: Re: Re: Re: Re: welder extension cord in reply to john, 01-09-2004 06:33:19  
Both of my old welders have no neutral in them ! They use ground only. So I would either flap the neutral in the breeze or double up the connections.
Can't hook something up to nothing.



[Log in to Reply]  [No Email]
Ben in KY

01-09-2004 11:27:45




Report to Moderator
 Re: Re: Re: Re: Re: Re: Re: welder extension cord in reply to Ben in KY, 01-09-2004 11:26:10  
The current on the ground wire thing is why they are now requiring the 4 wire cords, just a little hard to hook them up on only 3 terminals :)



[Log in to Reply]  [No Email]
buickanddeere

01-09-2004 22:04:43




Report to Moderator
 Re: Re: Re: Re: Re: Re: Re: Re: welder extension c in reply to Ben in KY, 01-09-2004 11:27:45  
240vac Welders have 240 fans inside. Current flows only through the two lines. No neutral required/needed. Again for you people who don't get it.The ground and neutral are two differnt wires and connections.To the same tinkers who have or contribute to livestock getting zapped at water bowls from tingle voltage. Only takes 0.2v to 0.3v to stress livestock. You do not connect a load in any way shape or form to the ground. Just to the chassis/frame etc to the bare or green ground. The ground is to prevent equipmet from floating above ground potential from induction. And to route fault current/lightening back to the earth electrode near the supply panel. Why do you think a 120vac device has a line,neutral and ground connection? The neutral and ground are kept separate for a reason.

[Log in to Reply]  [No Email]
Scott Green

01-09-2004 07:48:51




Report to Moderator
 Re: Re: Re: Re: Re: Re: welder extension cord in reply to john, 01-09-2004 06:33:19  
yes John , you are correct.



[Log in to Reply]  [No Email]
i r baboon

01-08-2004 11:17:00




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
if in doubt, u can double the romex. be blessed



[Log in to Reply]  [No Email]
Tom

01-08-2004 08:36:51




Report to Moderator
 Re: welder extension cord in reply to Keith, 01-08-2004 08:27:16  
I wondered the same thing when I made a 32 foot extension cord. I finally decided that, although the G in 6-2 is smaller, it is still 10 gauge wire, and that the breaker would trip long before the wire ever melted if one of the hots shorted.



[Log in to Reply]  [No Email]
Ray,IN

01-08-2004 23:49:24




Report to Moderator
 Re: Re: welder extension cord in reply to Tom, 01-08-2004 08:36:51  
I made my extension cord from entrance cable from an old mobile home. It's quite heavy to move around but works very well.



[Log in to Reply]  [No Email]
[Options]  [Printer Friendly]  [Posting Help]  [Return to Forum]   [Log in to Reply]

Hop to:


TRACTOR PARTS TRACTOR MANUALS
We sell tractor parts!  We have the parts you need to repair your tractor - the right parts. Our low prices and years of research make us your best choice when you need parts. Shop Online Today. [ About Us ]

Home  |  Forums


Copyright © 1997-2023 Yesterday's Tractor Co.

All Rights Reserved. Reproduction of any part of this website, including design and content, without written permission is strictly prohibited. Trade Marks and Trade Names contained and used in this Website are those of others, and are used in this Website in a descriptive sense to refer to the products of others. Use of this Web site constitutes acceptance of our User Agreement and Privacy Policy

TRADEMARK DISCLAIMER: Tradenames and Trademarks referred to within Yesterday's Tractor Co. products and within the Yesterday's Tractor Co. websites are the property of their respective trademark holders. None of these trademark holders are affiliated with Yesterday's Tractor Co., our products, or our website nor are we sponsored by them. John Deere and its logos are the registered trademarks of the John Deere Corporation. Agco, Agco Allis, White, Massey Ferguson and their logos are the registered trademarks of AGCO Corporation. Case, Case-IH, Farmall, International Harvester, New Holland and their logos are registered trademarks of CNH Global N.V.

Yesterday's Tractors - Antique Tractor Headquarters

Website Accessibility Policy